Control Unit

VK-3B

User Manual

Source page

Page 2

Open in PDF

Instruction manual VK-3B

Index

1.- Installation 3

2.- Description of the connections. 3

3.- Keys of access to the parameters of menu’s 4

4.- Modification of the parameter 4

A.- Modification of an alarm

B.- Modification of a parameter (not alarm)

5.- Programming structure of the menu’s 5

6.- Calibration of the unit 5 I.- Normal calibration

1.- Setting of the zero

2.- Adjust of the weight

II.- Calibration of the cell for direct transmission 1.- Setting of the zero

2.- Adjust of the weight

7.- Alarms 6

8.- Auxiliary Functions 6

9.- Mode of low consumption 7

10.- Electrical Characteristics 7

11.- Change of the fuse 7

12.- Presentation of errors 7

13.- Quick programming guide 8

Source page

Page 3

Open in PDF

Instruction manual VK-3B

1. Installation

2. Description of the connections.

AL-C (Relay contact of the Complete load) Change of the state if the load programmed in the parameter is overcome AL-S (Relay contact of the Overload) Change of the state if the load programmed in the parameter is overcome . AL-A (Relay of the Auxiliary) Change of the state if the load programmed in the parameter is overcome . HOLD (It activate with a tension between 24 & 220 V alternating or continuous). When the elevator is in progress, the measure of the weight is not good.The relay could be activated & the cabin display turns unstable. Activating the entrance of HOLD when the elevator gets in movement.The measure of weight is blocked,then the display presenting in intermittent, & the relay together with the cabin display conserves its state until this entrance is disabled, that should be after stopping the elevator.

OUTPUT OF CABIN DISPLAY It can give two types of output,that which you can select it on the parameter a) Output that is activated in an intermittent way when an overload takes place. The output has polarity, & it can be valid to activate a led and a buzzer (continuous current 7,5V máx.75mA). b) Activation of progressive display MB-D (Two threads connection without polarity).

Source page

Page 4

Open in PDF

Instruction manual VK-3B

3. Keys of access to the parameters of menu’s.

The unit has a menu to accede to the adjustment of the parameters. Pressing this key successively, will go going to all programmable parameters of the menu in a cycle way. To return to the visual presentation of weight, press the key several time until to arrive at the end of the menu, or just press it during 2 seconds.

Pressing this key enters in the selected option and once inside we will be able to select the digit to modify.

Pressing this key will modify the selected digit. Also by pressing this key when you are located on the selected parameter, the display presents its content.

4. Modification of the parameter

A) MODIFICATION OF AN ALARM 1) Press the key successively until being place on the desired alarm.

2) Press the key to enter in modification of the parameter, being the left digit in intermittent.

3) Put in the display the wanted value, using this keys .

4) Press to introduce the selected value.

5) Change the state of the relay with this key (ON/OFF).

6) Press twice to saved the change. In the event of only pressing once, you comes out without saving.

B) MODIFICATION OF A PARAMETER (NOT ALARM).

1) Press the key successively until being place on the desired paramete

2) Press the key to enter in modification of the parameter, being the left digit in intermittent.

3) Put in the display the wanted value, using this keys .

4) Press the key twice to save the assignated value. Then the display will present the next parameter.

Remarks: a) If you haven’t press 2 times, the operation will not stored, and the display presents again the parameters that you was modifying.

a) To modify the parameters & , please consult section No.6 (Calibration of the unit).

Source page

Page 5

Open in PDF

Instruction manual VK-3B

5. Programming structure of the menu’s

Presentation of the weight.

Alarm of complete load (ON/OFF)

Alarm of overload (ON/OFF)

Auxiliary Alarm (ON/OFF)

Adjust of zero setting

Adjust with a well-known weight

Adjust of the cells with direct load value

Chain compensation of the weight

Configuration of the cabin display, & the condition of relay

6. Calibration of the Unit

This section is necessary so that the unit knows the relationship between the signal of the cell and the weight introduced in the cabin. There are two ways to calibrate the unit: I) NORMAL CALIBRATION (Valid for all types of load cells).

1) SETTING OF THE ZERO: a) Situate in the option of menu .

b) Check that the cabin is empty and press the key ,& then press while is in intermittent the operation will be confirmed with a count-down. And when it finished, the display will present the

parameter .

Remarks: If you don't press the before finishing the intermittence, the operation will not stored, and the display presents again the parameter .

2) ADJUST OF THE WEIGHT: a) Situate in the option of menu . b) Introduce inside the cabin a well-known weight (It is recommended at least as minimum 50% of the

complete load) & press .

c) Put the value of the weight placed in the cabin using the keys .

d) To save the value press the key 2 times (The unit will start to count -down and the value will be save). Then the display will present the next parameter .

Remarks: If you haven't press the for the 2nd time, the operation will not stored, and the display

presents again the parameter .

Source page

Page 6

Open in PDF

Instruction manual VK-3B

II) CALIBRATION OF THE CELL FOR DIRECT TRANSMISSION (TCE MODEL) To fulfill this operation it is not necessary to introduce a well-known weight in the cabin

1) SETTING OF THE ZERO (same as the operation of the normal calibration). 2) ADJUST OF THE WEIGHT:

a) Situate in the option of menu .

b) To enter and be able to asigned a value press . c) Put the calibrated value of the cell using this keys . (This data comes at the end of the cables, and it belongs to the calibration value of the manufacturer.)

d) To save the value press the key 2 times(The value stored in the memory).then the display will

present the next parameter .

If you haven't press for the 2nd time the operation will not stored, and the display presents again the parameter .

7. Alarms

Remarks: 1) For the setting of the alarms, see section No.4(Modification of parameter). 2) It recommend to put the state of rest in ON because if a loss of data takes place in the programming, the relay always passes to the state OFF.

8. Auxiliary Functions

Option of the chain compensation. This option allows to compensate the difference of weight between floor taken place by the chain. To use this option it is necessary to introduce the approximate weight of the chain, keeping in mind that the allowed maximum value is 50kg. In the event of putting it to zero the chain compensation will be annulled. Allows to configure the output of cabin display and the condition of the relay. Config. Display of low consumption Output of cabin display ConF = 0 ON ON Intermittent activation (LED) ConF = 1 ON ON Progressive activation (MB-D) ConF = 2 OFF OFF Intermittent activation (LED) ConF = 3 OFF OFF Progressive activation (MB-D)

ColumnConfig.ColumnColumnDisplay of low consumptionColumnColumnOutput of cabin displayColumn
ON ON OFF OFF

Source page

Page 7

Open in PDF

Instruction manual VK-3B

9. Mode of low consumption

As the display is the most that consumes and it is not an element that is visible.It has been keep in mind a way of a low consumption, that once the display turns off automatically, the display presents a rotating segment to indicate that it is continuesly working.

Cases that the unit enters in the function of low consumption. 1) When connecting the unit to the power supply, it presents the weight during 3 minutes. And in the event of not touching any key, automatically it will pass to the mode of low consumption. 2) When it passed one hour since the last time that having played the key.

3) When the unit is presenting the weight, pressing the key during two seconds

Remarks: To leave the function of low consumption it is necessary to press any key.

10. Electrical Characteristics

VERSION 220 VAC VERSION 24 VDC Model: VK-3B Model: VK-3B Nominal tension : 220 Vac Nominal tension: 24 Vdc Nominal current : 60 mA Nominal current: 300 mA Nominal frecuency : 50-60 Hz Fuse: 800 mA Fuse: 100mA

11. Change of the fuse

1) Disconnect the unit 2) Open the unit removing the 5 screws that hold the back cover. 3) Take out the circuit of the box, and change the fuse that is in the vertical free mounting fuse holder located next to the transformer.

12. Presentation of Errors

Description Action

Load cell not well connected, damaged load cell Revise the connection of the load cell. or cut cable Negative Overflow The load cell is working in a contrary sense or it is not well connected. Positive Overflow. (The load cell is supporting a It is necessary to put a load cell that has a superior weight than the nominal value.) superior nominal value.

Polarity Error. (This error is detected when the Revise the connection of the load cell. unit adjusts the weight with the polarity of the load Repeat the setting of the zero and the adjust of cell changed). weight. Locate & eliminate the short circuit. (Note: In ver .24 Vdc this error is not present) Short circuit in the output of the cabin display (MB-D). Turn off the unit (VK) and connect it again so that the display will disappear Lost of datas in the memory. Program again the unit. Remarks: When an error takes place all the alarms will be activated and the elevator is blocked. If error takes place the contacts of the is open (RELAY = OFF). 7

VERSION 220 VACVERSION 24 VDC
Model: VK-3B Nominal tension : 220 Vac Nominal current : 60 mA Nominal frecuency : 50-60 Hz Fuse: 100mAModel: VK-3B Nominal tension: 24 Vdc Nominal current: 300 mA Fuse: 800 mA
ColumnDescriptionColumnAction
Load cell not well connected, damaged load cell or cut cableRevise the connection of the load cell.
Negative OverflowThe load cell is working in a contrary sense or it is not well connected.
Positive Overflow. (The load cell is supporting a superior weight than the nominal value.)It is necessary to put a load cell that has a superior nominal value.
Polarity Error. (This error is detected when the unit adjusts the weight with the polarity of the load cell changed).Revise the connection of the load cell. Repeat the setting of the zero and the adjust of weight.
Short circuit in the output of the cabin display (MB-D).Locate & eliminate the short circuit. (Note: In ver .24 Vdc this error is not present) Turn off the unit (VK) and connect it again so that the display will disappear
Lost of datas in the memory.Program again the unit.

Source page

Page 8

Open in PDF

Instruction manual VK-3B

13. Quick programming guide

1. Install the sensor and connect it to the unit control.

To connect properly the sensor to the unit control, please see section No.1 (Installation)

This section is to knows quickly the keys of this unit. a) To find the parameter that is wanted to change press successively and to accede to the parameter

press

b) Modify using this keys ,

c) To save the data press 2 times

2. Before to start to calibrate the unit control, please be advise to do the following: a) Down the cabin to the lower plant of the building. (or in the half of the itinerary) b) Bounce inside the cabin to avoid possible hooks on the guide rail.

3. Most important parameters to calibrate step by step: 1. Set the Zero of the unit with the empty elevators:

- Situate in the parameter

- Press , and will start to count-down. 2. Adjust of the Weight (Peso): - Put a well known weight inside the cabin ( at least 50% of the complete load)

- Introduce in the parameter the value of the load that has been placed in the cabin using this keys

, then to save it press 2 times and the unit will start to count-down.

3. Put in the value of the load, starting from which is required to activate the alarm of complete load.

4. Put in the value of the load, starting from which is required to activate the alarm of overload.

5. Put in the value of the load, starting from which is required to activate the alarm of auxiliary (if it will be used). Note: It is important to calibrate the setting of zero before doing the operation of the adjust of weight.

Dinacell Electrónica sl. All rights reserved. The contained information in this document is subject to changes without previous notice. The content shown here should be used as general product information. It should not be interpreted as a guarantee of quality or durability. Electronic Dinacell shall not be liable for technical or editing errors or omissions contained in this document.

D2393-00 29/08/2024

Technical data

Highlighted specifications

SpecificationValuePage
VERSION 220 VACVERSION 24 VDC7
Load cell not well connected, damaged load cell or cut cableRevise the connection of the load cell.7
Negative OverflowThe load cell is working in a contrary sense or it is not well connected.7
Short circuit in the output of the cabin display (MB-D).Locate & eliminate the short circuit. (Note: In ver .24 Vdc this error is not present) Turn off the unit (VK) and connect it again so that the display will disappear7
Lost of datas in the memory.Program again the unit.7