DinacellUser manual

OMEGA NG User manual

Technical reference for OMEGA NG User manual with 24 pages, 6 tables, searchable navigation and precise source-page references.

Chapters
1
Pages
24
Language
English
Format
PDF
OMEGA NG User manual
First page of the technical document

Complete web edition

The complete manual in one reading flow

Pages follow the exact source order. Searchable text is also available for every page.

1

Complete document

Pages 1 to 24

Source page

Page 1

Open in PDF

[iN Dinacell ING OMEGA LOAD WEIGHING DEVICE CANopen LIFT User manual ee , aod? waht u _-

Source page

Page 2

Open in PDF

User manual OMEGA/NG

INDEX

1. DESCRIPTION AND MAIN FEATURES.......................................................... 3 2. DISPLAY AND CONTROL BUTTONS ............................................................ 3

3. DIMENSIONS, INSTALLATION AND CONNECTIONS .................................. 4

4. MENU STRUCTURE........................................................................................ 5 5. HOW TO VISUALIZE OR CHANGE PARAMETERS ..................................... 6

6. DEVICE INFO .................................................................................................. 7

7. SYSTEM CONFIGURATION ........................................................................... 8 8. ALARMS CONFIGURATION ......................................................................... 10

9. CHAIN COMPENSATION .............................................................................. 12

9.1. New Chain Compensation ........................................................................ 12 9.2. Submenu Chain ........................................................................................ 12

9.3. Chain Compensation Adjust ..................................................................... 13

9.3.1. Software Compensation .................................................................... 13 9.3.2. Hardware Compensation ................................................................... 13

9.3.3. Auto-Zeroing Compensation .............................................................. 14

10. ADDITIONAL FUNCTIONS ........................................................................... 15 10.1. Hold function ............................................................................................. 15

10.2. Analog output (Optional) ........................................................................... 15

10.3. Cabin Display (Optional) ........................................................................... 16 11. CANOPEN PARAMETERS (ONLY RELEVANT FOR OMEGA-C MODELS ) .......... 16

12. ERROR CODES AND TROUBLESHOOTING .............................................. 18

13. ELECTRICAL SPECIFICATIONS ................................................................. 18 14. NG CONECTION ........................................................................................... 19

14.1. Wifi NG Connection .................................................................................. 19

14.2. Firmware Update ...................................................................................... 19 15. WIRE ROPE TENSION EQUALAZING ......................................................... 20

15.1 Wire Rope Tension checking Tool ............................................................ 20

15.2 Assistance to the wire rope tension adjustment ........................................ 21 16. QUICK CONFIGURATION GUIDE ................................................................ 23

Source page

Page 3

Open in PDF

User manual OMEGA/NG

1. DESCRIPTION AND MAIN FEATURES

OMEGA/NG Unit control is a Load Weighing device of the (NG) New Generation units from Dinacell Electronic with CanOpen-Lift CIA 417 Integrated.

The Main features of this unit are:

- Measures, monitors and limits load in elevators. - Up to 12 Individual Rope Tension monitoring.

- Wire Rope Tension adjustment. - 5 Digits display with 4 LEDs for alarm indication and 2 LEDs for Can Status

- Hold Input - 4 Alarms Thresholds (Full Load, Over Load, Zero Cabin, Slack Rope Tension ) - 4 Relays output

- 0-10v Analog Output - 4-20ma Analog Output

- Cabin Display Output - CanOpen-Lift CiA 417.

- Software Chain compensation. - Hardware Chain compensation.

And the new features of Our NG devices - Remote WIFI Programming( NG ) - USB connection for firmware upgrading.

2. DISPLAY AND CONTROL BUTTONS

Functions of control buttons: The unit is equipped with a menu by which the individual setting parameters can be displayed or modified. a. By Pressing this key for 2 Seconds Enter/exit the menu b. By Pressing this key inside the menus will navigate through parameters. c. Accept and save modified values when modifications are on progress. a. During menu navigation: Enter to modify a parameter. b. While modifying a parameter: Chose digit to change.

a. During menu navigation: Show the stored value of the selected parameter. b. While modifying a parameter: Change the blinking digit incrementally from 0 to 9.

Source page

Page 4

Open in PDF

User manual OMEGA/NG

Note: After two minutes without any operation, the unit automatically returns to the total weight measure display, independent of the menu item previously selected.

Led Functions

AL1 Full Load Alarm Indicator AL2 Over Load Alarm Indicator AL3 Zero Load Level Indicator (Empty Cabin)

AL4 Slack Rope tension indicator STA Led status ( For CanOpen: Status Led ) ERR Error ( For CanOpen: Error Led)

3. DIMENSIONS, INSTALLATION AND CONNECTIONS

ColumnLedColumnColumnFunctionsColumn
AL1Full Load Alarm Indicator
AL2Over Load Alarm Indicator
AL3Zero Load Level Indicator (Empty Cabin)
AL4Slack Rope tension indicator
STALed status ( For CanOpen: Status Led )
ERRError ( For CanOpen: Error Led)

Source page

Page 5

Open in PDF

User manual OMEGA/NG

1 Sensor inputs Up to 12 USB Connectors for easy plugging

Output It provides two types of output: INC: Progressive display MB-D (two wire connection without Cabin display 2 polarity). output LED: If overload, it will be an intermittent voltage of 5V (max. 30mA) with the polarity shown in the figure. This output reflects the sensors signal over the range 0-10V and 3 Analog outputs 4-20mA. Common signal is GND. (See the ADDITIONAL FUNCTIONS chapter). 4 Can Open Input 24 VDC power supply and Can Bus in an Open Style connector Relay Terminals of the alarm relays. 5 connections for (See the alarms section in chapter 8) alarms This function will be activated if an input voltage from 24 to 230V (DC or AC) is 6 HOLD input applied. (See the ADDITIONAL FUNCTIONS chapter). 4. MENU STRUCTURE The menu has the cyclic structure shown in the following figure.

Press button for 2 seconds to enter and then press it repeatedly to move from a parameter to another. Press it for 2 seconds to exit. Weight indication. Display the value of the measured load

Press Menu for 2 Seconds

Shows Identification Data of the unit

System calibration. These menus shows all parameters related with the load cell Configuration.

Alarm Levels configuration.

Chain compensation options

CanOpen Configuration. (Only relevant for OMEGA-C models ) Load Cell mv/v. signal value.

Led or Cabin Display Output (Only relevant for OMEGA-4RM models )

Pressing Menu for 2 seconds inside the internal navigation menu will end the menu navigation and return to Display the value of the measured load

Cabin display output
Analog outputs
Can Open
Relay connections for alarms

Source page

Page 6

Open in PDF

User manual OMEGA/NG

5. HOW TO VISUALIZE OR CHANGE PARAMETERS

Once inside any menu and displaying the parameter to be viewed or changed:

 Press to display the current value.

 Press to select the parameter to be modify :

 Press to choose the digit position to change ( Flashing )

 Press to change the value of the Current Flashing digit position. (if there’s no flashing digit,

change the value with key directly)

 Press twice to save the value.

If button is not pressed again before display Flashing ends (10 seconds), the parameter value will not be changed.

After any of these operations, the display will show the current parameter.

Source page

Page 7

Open in PDF

User manual OMEGA/NG

6. DEVICE INFO

All new NG units store some important information in this menu in order to build wireless connections with any remote future unit developed by Dinacell Electronica. All parameters can be read in this submenu.

Submenu Press to enter Check value Enter to modify

Add: NG Network Address of the unit.

Id_nu: Identification number of the unit. Unique identification for each unit.

Equip: Model of unit. Valid Values: OME

Ver: Firmware Version of Unit OMEGANG Valid Values: 1.00 and above

V_Har: Hardware Version of Unit OMEGANG

APi: ApiVersion of NG Dinacell Network Valid Values: 100 and above

VOLt: Internal Power supply Voltage of unit OMEGANG Valid Values: (around 24 volts )

rESE: Reset all parameters value to Factory defaults. All calibration data will be lost

Source page

Page 8

Open in PDF

User manual OMEGA/NG

7. SYSTEM CONFIGURATION

This section describes how to configure the Unit to obtain the best measure accuracy. The configuration

is done in Menu. Press Check value Enter to modify to enter nSen: Number of sensors connected to ropes or cables. If this parameter is not set correctly, the unit will show Err1 and alarm relays will be activated. Iref: Initial Reference of the sensors. This operation must be done with the Sensors uninstalled on the ropes.

Note: It is mandatory to do the iref operation if Wire Rope Tension balancing is going to be adjusted. Units: Display Weight units. Available units are Kilos/Pounds

SusPE: Type of suspension at installation: 1:1 2:1 3:1 4:1

Zero: Zero point adjustment With empty elevator. Store a Countdown value for Zero and load calibrating parameters

Load: Well known weight applied inside the elevator to do the weight calibration of the unit. (It is recommended to set up to 60% of the nominal load of the elevator.)

Cell: Nominal load cell sensibility. This value is calculated when LOAD operation is done. User shouldn ́t modify this value. ( If this parameter is modified the previous calibration settings will be overwritten) pSen: indication of individual Sensor Rope weights. On the display appears the weight in units selected (e.g. 100kg) alternating with the Sensor number ( Se 1)

Source page

Page 9

Open in PDF

User manual OMEGA/NG

Calibration process:

1) Install the control unit with the information of the INSTALL AND CONNECTIONS chapter.

2) Connect Load Cell to the OMEGANG 3) Power up the unit with the correct voltage (see the ELECTRICAL SPECIFICATIONS chapter).

4) Go to Submenu:

5) Detail Calibration Procedure: Follow next steps to set a precise Load Measuring system

5.1 ) Select number of sensor ropes. 5.2 ) Do and Iref Operation with sensors not installed on the ropes.

5.3 ) Select display measuring units. Available units are Kilograms or Pounds

5.4 ) Select Suspension. By default 1:1 is selected

5.5 ) Zero adjustment:

a) Install sensors on the ropes when using SWK, SWR or LCA.

b) Select Submenu Zero by pressing c) Change countdown value if desire. d) Press menu and display will start flashing

e) Make sure elevator is empty and confirm operation by pressing again. f) The countdown will start. During this time, the car weight must not change.

5.6 ) Load Point adjustment: With This function the Unit will be calibrated with the best accuracy. Put a well known weight into the cabin. Is recommendable a 60% of elevator duty load.

To make the Load point adjustment:

a) Select Submenu Load by pressing b) Set the value with the total Load added into the elevator.

c) Press menu and display will start flashing

d) Confirm operation by pressing again. e) The countdown will start. During this period of time, the car weight must not change

5.5) This parameter stores the Sensor Sensibility. Cell value is automatically calculated after a Load Point adjustment. If Cell Value is changed, the previous calibrating process will be overwritten.

Source page

Page 10

Open in PDF

User manual OMEGA/NG

8. ALARMS CONFIGURATION

The alarms values correspond to the load threshold at which each relay change its state.

The relays allows to be configured individually as make or break contact Alarms are activated when their threshold is exceeded. The Unit OMEGANG has 4 different alarms:

AL-1 (Full Load, Relay #1):

Change of state when exceeding the load programmed in AL-2 (Over Load, Relay #2):

Change of state when exceeding the load programmed in

AL-3 (Zero Load, Relay #3):

Change of state when falling below the load programmed in Note: This alarm is active below Alarm3 Threshold.

AL-4 (Rope Tension Difference and Slack Rope Tension, Relay #4): Change of state if any rope has a slack rope tension or if any rope deviates from the average of all

other ropes at least by the percentage programmed in .

The working procedure of the relays as a make or break contact can be changed for each alarm output

using the parameter. Valid values are (Close) for the operating mode MAKE and (Open)

for the operating mode BREAK. Close is a normally closed relay and OPEn is a normally open relay. Alarm LEDs indicators will be activated when the display measured value overload corresponding

alarm level

Note: LEDs are not related to relay state but alarms levels.

10

Source page

Page 11

Open in PDF

User manual OMEGA/NG

How to configure alarm settings:

Go to Submenu Press Check value Enter to modify to enter Level: Alarm 1 Level Threshold for Full load alarm. rStA: Relay Status. When alarm 1 is deactivated (Idle Mode) (Only relevant for OMEGA-4R models )

Level: Alarm 2 Level Threshold for Over load alarm.

rStA: Relay Status. When alarm 2 is deactivated (Idle Mode) (Only relevant for OMEGA-4R models )

Level: Alarm 3 Level Threshold for Zero Load alarm.

rStA: Relay Status. When alarm 3 is deactivated (Idle Mode) (Only relevant for OMEGA-4R models ) Level: Alarm 4 Level percentage Threshold for Rope tension difference and slack rope alarm.

rStA: Relay Status. When alarm 4 is deactivated (Idle Mode) (Only relevant for OMEGA-4R models )

All Displayed weights and alarm thresholds are shown in selected units. All internal calculations are made in kg, therefore, rounding errors are possible

11

Source page

Page 12

Open in PDF

User manual OMEGA/NG

9. CHAIN COMPENSATION

9.1. New Chain Compensation

The New Generation of Load Weighing Devices has the newest Software for chain

compensation. It offers several options to improve the accuracy to compensate the weight of the chain.

In this Submenu, the user can choose between three options, no compensation, software compensation and hardware compensation.

9.2. Submenu Chain

Submenu Press Check value Enter to modify to enter Type: Type of chain compensation applied. User can choose between hardware compensation, software compensation or none compensation Value: Max Chain value to compensate. At installation. Valid Values : 0-600

C_Bot: Chain zero operation at the ground floor

C_Top: Chain load operation at the top floor

C_Har: Real chain load value compensated by hardware measure in selected units

ChCEL: Nominal Chain load cell sensibility. This value is calculated when C_Bot or C_top operation is done. User shouldn ́t modify this value. ( If this parameter is modified the previous calibration settings will be overwritten)

C_Sof: Chain load value compensated by software estimation in selected units

Time 1: Time to get hold weight before Hold is activated

Time 2: Time to get hold weight after Hold is deactivated

12

Source page

Page 13

Open in PDF

User manual OMEGA/NG

9.3. Chain Compensation Adjust

The NG Series has new advanced chain compensation. To use all the features of new

compensation is necessary to adjust some parameters in Menu.

There are two types of compensation.

 Software chain compensation: When selected, the unit compensate the chain with hold signal

activations/ deactivations.  Hardware chain compensation: When selected, the unit compensate the chain with the on real

time weight of the chain. This can be done using the auxiliary Load Cell input for chain

compensation and adjusting the parameters for hardware compensation. Note: To deactivate all chain compensations just set Type parameter to none.

Set Type to None value.

9.3.1. Software Compensation This function allows compensate the difference of weight between floors produced by the chain. The unit needs the HOLD signal to be active when the doors close to compensate the

weight during the elevator movement.

To configure the software compensation:

Set Type to SoFT value. 

Set the estimated weight of the chain. This parameter will be the maximum value  compensated by software compensation

In this parameter you can check the value the OMEGANG is compensating by software each  time the HOLD signal is deactivated

When using software compensation, Auto_Zero compensation will be activated automatically.

9.3.2. Hardware Compensation

In some installations ( the largest ones), software chain compensations doesn`t work perfect due to different friction in the rails between floors, weight changes during long

elevator travels, or just any auto_zero is done cause elevator never stops. These problems can be solved with Hardware compensation.

It is mandatory to plug an auxiliary Sensor (Load Cell for chain compensation) when

hardware compensation is selected. Otherwise Err1 will flash in the display.

Auto_Zero compensation will be also deactivated automatically

A system Configuration (Point 7) must be done previous to set the Hardware compensation parameters.

13

Source page

Page 14

Open in PDF

User manual OMEGA/NG

Set Type to Hard value 

Take the elevator to the ground floor and set C_Bot To Yes. A Countdown will  start.

Take the elevator to the Top floor and set C_TOP To Yes. A Countdown will start 

In this parameter you can check the value the OMEGANG is compensating by hardware  with the chain load cell

9.3.3. Auto-Zeroing Compensation

The Auto_Zero compensation is designed to automatically remove small measurement error

lower than parameter

The Auto-Zero function will happen whenever the OMEGANG measures a static offset of ±

for a period of at least 120 seconds. During this time the measured load must not change

by more than 20kg. The OMEGANG applies an internal compensation value equal to the inverse value of the currently measured offset.

The Auto_Zero compensation value is stored in internal memory. After power cycling the measure in the display will be the same. To eliminate the Auto_Zero compensation, a Zero operation should be

done.

14

Source page

Page 15

Open in PDF

User manual OMEGA/NG

10. ADDITIONAL FUNCTIONS

10.1. Hold function

During the elevator travel, the measured loads can heavily fluctuate due to friction in the rails,

loads movements, etc. When a voltage in the range 24-230V (DC or AC) is applied in this input, the unit holds the last stable measure of weight acquired.

The voltage must be applied when the doors close and it must be removed as the doors open.

This ensures that the movement of the cabin will not affect the weighing process and therefore, no alarms or relay will be activated during elevator travel.

To improve the hold of a stable measure two parameters have been added at CHAIN menu

and .

As some installations sets the HOLD input at the same time it closes the doors, sometimes the last measure obtained is not as stable as desire. The same issue can happen when removing the HOLD

input and the doors Open.

 Time in tenth of seconds to take the measure before the hold. Signal is active.

 Time in tenth of seconds to update the measure after the hold. Signal is released.

Note: With T_1 = 10 and T2 = 15: If hold signal is activated, then, the OMEGANG will take as a valid measure the last stable weight

value that was stored 1 second before hold was activated. Then when hold is released the first stable value will be taken 1.5 seconds after the hold signal is deactivated.

This option offers great flexibility to resolve problems in some critical installations.

10.2. Analog output (Optional)

This unit is provided with two analog outputs (Voltage and current output). Both Outputs are

active and operative at same time.

This function reflects the sensors signal over the range between ZERO and the value sets for ALARM1 (full load):

Output Range

When weight ≤ 0kg 0 V 0-10 volts (empty elevator) ( 0-5 Optional ) When weight ≥ ALARM1 10 V (elevator at full load) ( 5V Optional ) When weight ≤ 0kg 4 mA (empty elevator) 4-20 mA When weight ≥ ALARM1 20 mA (elevator at full load) 15

ColumnOutputColumnColumnRangeColumnColumn
When weight ≤ 0kg (empty elevator)0 V
When weight ≥ ALARM1 (elevator at full load)10 V ( 5V Optional )
When weight ≤ 0kg (empty elevator)4 mA
When weight ≥ ALARM1 (elevator at full load)20 mA

Source page

Page 16

Open in PDF

User manual OMEGA/NG

Example: Once the system is completely configured, if ALARM1 is set to 400 kg and if unit measures 200kg then;

 0-10V Output will be 5V.  4-20mA output will be 12mA.

10.3. Cabin Display (Optional)

It provides two types of output depending on the CDISP parameter:

LED Indicator: Under overload it will be an intermittent voltage of 5V (max. 75mA) with the polarity shown in the figure. LED Incremental Progressive display MB-D (two wire connection without polarity)

11. CanOpen PARAMETERS (Only relevant for OMEGA-C models )

Dinacell electronic is member of the CiA ( Can In Automation ), Vendor-ID 00000361

OMEGANG-C accomplish with the CanOpen-Lift CiA 417 profile.

Some important CanOpen Parameters can be modified from this Submenu as, Baud rate and Node ID. Weigh change detection is a threshold that will send a PDO message when the weight change overpasses the value. Node Id: Node Id of the CanOpen Load Weighing Device

Baud Rate: Baud Rate of the CanOpen Device. 125kb or 250kb Supported for the 417 Profile.

Detection of weight change: Units required for detecting a change of weight in the cabin and send a Can Message by load changed. (1,2,5,10,20,25,50,100,250)

Door Contact: If a Car Door Unit is present at the installation, the OMEGANG-C can Read the Door status just setting this parameter to “Yes”. When the Door closes the Measure on the Display is Hold and it will not change until the door Opens. . CanOpen Version supported: Actual version supported 2.0.0

16

Source page

Page 17

Open in PDF

User manual OMEGA/NG

 CanOpen Specifications FEATURES NMT NMT Slave Error Control Node guarding Life guarding Heartbeat consumer Boot-up Yes Node ID range From 1 to 127 Node ID Proprietary LMT-services Keyboard CanOpen bit-rates 10 kbit/s 20 kbit/s 50 kbit/s 125 kbit/s 250 kbit/s 500 kbit/s 1000 kbit/s Type of bit-rate adjustment Proprietary LMT-services Keyboard RPDOs 1 TPDOs 1 PDO modes Synchronous (cyclic) Synchronous (acyclic) Event-triggered Remotely-requested Triggered by event-timer PDO linking Yes PDO mapping Static SDO server 1 SDO client No Emergency Producer Yes Emergency Consumer Yes Sync Producer No Sync Counter No Time stamp No Additional Functions None Supported application layer CiA 301 V 4.2 Supported Frameworks CiA 303 V 1.3 Device Profiles CiA 417: CanOpen application profile for lift control systems V2.0.0.0 17

ColumnFEATURESColumnColumnColumn
NMT
NMT Slave
Error Control
Node guarding
Life guarding
Heartbeat consumer
Boot-up
Yes
Node ID range
From 1 to 127
Node ID
Proprietary
LMT-services
Keyboard
CanOpen bit-rates
10 kbit/s
20 kbit/s
50 kbit/s
125 kbit/s
250 kbit/s
500 kbit/s
1000 kbit/s
Type of bit-rate adjustment
Proprietary
LMT-services
Keyboard
RPDOs
1
TPDOs
1
PDO modes
Synchronous (cyclic)
Synchronous (acyclic)
Event-triggered
Remotely-requested
Triggered by event-timer
PDO linking
Yes
PDO mapping
Static
SDO server
1
SDO client
No
Emergency Producer
Yes
Emergency Consumer
Yes
Sync Producer
No
Sync Counter
No
Time stamp
No
Additional Functions
None
Supported application layer
CiA 301 V 4.2
Supported Frameworks
CiA 303 V 1.3
Device Profiles
CiA 417: CanOpen
application profile for lift
control systems V2.0.0.0

Source page

Page 18

Open in PDF

User manual OMEGA/NG

12. ERROR CODES AND TROUBLESHOOTING

When the unit detects some anomaly it will show an error code from the following table:

Error description Action Load cell is not properly connected, or its Check the load cells connection. cable is damaged. Negative overflow. The load cell is giving a Check the load cell connection. It too high negative signal. should be no negative charge. Positive overflow. Load cell is holding a higher Change the load cell by another with load than its nominal value. higher nominal load. Loss of data in memory. The unit must be reset to its default Notice: When this error appears, relays will values change to ACTIVATE state. Load cell with very low sensibility. The unit Adjust the zero and Load again. was not properly adjusted or load cell has a Change the load cell by another with low nominal value. lower nominal load. Load cell is not properly connected, or its Check the chain load cell connection... cable is damaged, or wrong number of If no Hardware chain compensation sensors set in parameter nSens. desired, change Type parameter at menu chain to None or soft

Important: When an error appears, all alarms are activated and the elevator remains blocked.

RESTORING THE FACTORY SETTINGS (Only in case of configuration problems)

Just go to menu and set option to yes:

13. ELECTRICAL SPECIFICATIONS

Short-circuitable. Power supply characteristics It is not necessary to replace any fuse. Nominal voltage 10-40 Vdc Maximum current <200mA

Relays Contacts 1A - 30V DC (Nominal Switching Capacity) 0.3A - 125V AC HOLD Input 24V-230V AC/DC

Box IP-50 V0 fireproof plastic.

18

ColumnError descriptionColumnColumnActionColumn
Load cell is not properly connected, or its cable is damaged.Check the load cells connection.
Negative overflow. The load cell is giving a too high negative signal.Check the load cell connection. It should be no negative charge.
Positive overflow. Load cell is holding a higher load than its nominal value.Change the load cell by another with higher nominal load.
Loss of data in memory. Notice: When this error appears, relays will change to ACTIVATE state.The unit must be reset to its default values
Load cell with very low sensibility. The unit was not properly adjusted or load cell has a low nominal value.Adjust the zero and Load again. Change the load cell by another with lower nominal load.
Load cell is not properly connected, or its cable is damaged, or wrong number of sensors set in parameter nSens.Check the chain load cell connection... If no Hardware chain compensation desired, change Type parameter at menu chain to None or soft
ColumnColumnColumnColumnShort-circuitable.Column
Power supply characteristics
It is not necessary to replace any fuse.
Nominal voltage10-40 Vdc
Maximum current<200mA
Relays Contacts1A - 30V DC
(Nominal Switching Capacity)0.3A - 125V AC
HOLD Input24V-230V AC/DC
BoxIP-50 V0 fireproof plastic.

Source page

Page 19

Open in PDF

User manual OMEGA/NG

14. NG CONECTION

All New Dinacell Units have a special feature called NG Connection (New Generation connections)

The main function of the NG connection is to connect to android Smart phones for Unit calibration, and reading Pen Drives for software updating.

14.1. Wifi NG Connection

To use all advanced features of NG Connection, user needs to connect the WRCTNG adapter to the unit OMEGANG and Dinacell TOOLS Application software must be installed in a smart Phone or Laptop. Users can download the Dinacell Application “Weighing NG” from Google Play Store market or from Apple Store.

With the New WRCTNG adapter connected to the NG Connection of the OMEGANG, users can: a) Get all parameter values of the unit in real time.

b) Calibrated the unit without using the key board. c) Test the installation performance.

d) Make studies of the measures in the installation to adjust rope tensions, guides, detect friction problems during

travels. e) Save all Calibrating parameters data in a Pdf report.

f) Send reports by mail. g) Stores all installation calibrations in a single phone.

h) And so on, cause software is in continuous development.

14.2. Firmware Update It is possible to update the firmware of any NG Device using the NG connection and a Flash Pen drive.

Follow next steps to enter in Boot loader mode for firmware updating: a) Copy new firmware (.CYP file) in the Flash Pen drive.

b) Plug the Pen drive in the auxiliary USB cable adapter from USB to Mini USB. c) Switch off the unit OMEGANG by removing the power supply.

d) Press key and apply power to the unit with the key pressed. ERR LED will flash each second, and 5 Digits display will be switched off. e) Plug the Mini USB cable on the NG connector. STA LED Will be ON and ERR LED will Flash

Faster (each 0.5 second) f) Be patient and Wait until unit reboots. The process can take up to a minute.

g) When programming ends the Unit Will reboot automatically. 19

Source page

Page 20

Open in PDF

User manual OMEGA/NG

15. WIRE ROPE TENSION ADJUSTMENT

This section explains how to check the tension of all wire ropes of the installation. All ropes

should carry the same tension. Equally tensioned ropes improve ride quality and extend life of ropes and sheaves.

Nowadays most elevator systems have multiple wire ropes attached to the cabin and

counterweight. This ropes normally run over a traction sheave or pulley just to move the cabin up and down the hoistway.

When some ropes have more tension than other, the ropes with lower tension will slide over the

pulley and can produce a crown groove wear at the sheave. It is possible to detect this wear by rope slapping, vibrations on the cables, or metal dust on the pulley.

Normally, the system works better if all the ropes have similar tension (about ± 5%) of the nominal load of the installation.

Although some installers manage to adjust the rope tension manually just touching the ropes or

Just tuning the installation plucking each rope as a harp string, the best way to do this operation is

measuring the load on all the ropes and displaying it in real time.

Usually Load weighing devices manufactures have dedicated and expensive tools to do this operations.

But the OMEGANG, can be used not only as a good Load Weighing device but as an additional low cost rope tension balancing tool also.

And as the unit will be installed for life you will have a permanent tool to adjust wire rope tension

and detect slack ropes at the installation in real time.

15.1 Wire Rope Tension checking Tool

The only tool needed to adjust the wire rope tension is the WRCTNG dongle and a Smartphone a tablet or a laptop. Then from the rope tension screen you will visualize the load of each rope in real time

Now it is possible to adjust the tension of each rope to make then equal.

20

Source page

Page 21

Open in PDF

User manual OMEGA/NG

15.2 Assistance to the wire rope tension adjustment With this assistant tool you will be guide to adjust each rope with the adequate load just to

accomplish the desired target. To enter this mode just push ADJUST label

Following the suggested steps, you can apply the precise load to each rope to perform the whole "wire rope tension" process, just in a few minutes.

21

Source page

Page 22

Open in PDF

User manual OMEGA/NG

Now, you can check the final result of the adjustment process.

You can save all your installations data on your Smartphone, tablet or laptop. You can save as

many installations as you desire (the only limitation is the memory of each device). Sending reports by mail or create your own PDF reports are also possible from the tool.

Laptop Configuration Software:

Same operations can be done from a laptop or any computer with WIFI connection.

22

Source page

Page 23

Open in PDF

User manual OMEGA/NG

16. QUICK CONFIGURATION GUIDE

 Parameters checking or modification

Press repeatedly to find the desired parameter Press 2 sec. to enter Press x2 Press 2 Check Enter to Change Choose to save sec. to exit value modify digit digit value  Quick System configuration

1. Install the OMEGANG in an appropriate location. 2. Connect all sensors to the unit and relay outputs if necessary.

3. Go to submenu

4. Set the number of sensor (ropes) of the installation. 5. Do and operation for all sensors.

6. Set to kilo or Pounds

7. Set the Suspension Factor . 8. Install the sensor on the Ropes.

9. Empty the elevator and set the countdown value for calibrating operations. Confirm the value

.for Zero Operation. A countdown will start. 10. Set a well-known weight inside the cabin and adjust parameter with the weight added. A

countdown will start.

11. Set the alarms thresholds for each alarm and the activation state for each relay. 12. If chain compensation is desired, select the type of compensation you want to use.

If software compensation is selected then set the estimated weight value in Menu Chain

option.

If Hardware compensation is selected then an operation must be down at the bottom floor, and afterwards an operation should be done at the top floor of the installation.

(Remember to do both operations with no weight inside de cabin).

23

Source page

Page 24

Open in PDF

User manual OMEGA” y- ON Dinacell Electronica s.1. Dinacell Pol. Ind. Santa Ana C / El Torno N° 8 - 28522 - Rivas Vaciamadrid - Madrid ww Tel.: +34 913 001 435 - Fax.: +34 913 001 645 E-mail: dinacell@dinacell.com - http: //www.dinacell.com Eskan Faraz DELTA Compony Unit 408,4th Floor,Alvand Building, Ebrahimi St, Marzdaran St - Tehran,lran /f\\ Office: +98 21 4438 6406 , +98 21 4438 6416 DELTA Fax: +98 21 4438 6376 24

Technical data

Highlighted specifications

SpecificationValuePage
Load cell is not properly connected, or its cable is damaged.Check the load cells connection.18
Negative overflow. The load cell is giving a too high negative signal.Check the load cell connection. It should be no negative charge.18
Positive overflow. Load cell is holding a higher load than its nominal value.Change the load cell by another with higher nominal load.18